IronAxis

IronAxis Industrial Supply

IronAxis is a U.S.-based B2B supplier of industrial equipment, instruments, machinery, food processing systems and new energy solutions for manufacturers, labs and engineering companies.

Contact Us

info@ironaxis-supply.com

More Services More Services More Services More Services More Services More Services
VC5000A Power Quality Analyzer

Chongqing Sell Best Technology Co., Ltd

The VC5000A Power Quality Analyzer is a three-phase, multi-function, intelligent, and simple comprehensive test instrument specially developed for on-site testing. It is easy to use, large LCD color sc...

EV Charging Infrastructure Chongqing Sell Best Technology Co., Ltd 24 Dec 2025 ( )

Get Your Quote Now : US$ 1300/ Piece

The VC5000A Power Quality Analyzer is a three-phase, multi-function, intelligent, and simple comprehensive test instrument specially developed for on-site testing. It is easy to use, large LCD color screen display, high resolution, a bilingual operation interface in Chinese and English, and vibration-proof structure shell. It can measure 4 currents (ABC three-phase and neutral wire current),4 voltages (ABC three-phase voltage and neutral wire-to-ground voltage), the peak value of current and voltage, the maximum and minimum values within period of time, three-phase current Balance, short-term voltage flicker, transformer K factor, active power, reactive power, apparent power, power factor, displacement power factor, active energy, reactive energy, apparent energy, harmonic ratio, total harmonic distortion, display current and voltage real-time waveforms, phasor diagrams, and harmonic ratio bar graphs; dynamically capture instantaneous changes in voltage and current, monitor starting current, monitor various power parameters and generate alarm events list, record test data fora long time and generate trend curves Picture and other various functions.

Features

Real-time monitoring of power quality parametersReports and charts can be providedImprove the reliability and stability of the power gridPower quality analysis, diagnosis of grid qualityRemote monitoring, real time monitor power qualityFailure early warning, detection of potential equipment failuresCan record historical data to facilitate analysis and prediction of power quality change trendsAutomatic alarm, automatically send an alarm signal when the power quality is abnormalOptimize grid operation, reduce energy consumption, and improve grid efficiency.

Application

  • Energy Metering and Billing
  • Smart grid construction and operation
  • Power system operation monitoring and analysis
  • Industrial production equipment power quality monitoring and analysis
  • Power quality improvement program design and implementation
  • Power system installation and operation inspection
  • Construction and operation monitoring of renewable energy power stations
  • power quality monitoring and management

Specification

ParameterValue
Frequency40-70Hz / 0.01Hz / ±0.03Hz
True RMS Voltage1.0-1000V / 0.1 / ±(0.5%+5dgt)
True RMS Line Voltage1.0-2000V / 0.1 / ±(0.5%+5dgt)
DC Voltage1.0-1000V / 0.1 / ±(1.0%+5dgt)
True RMS Current10mA-9000A / 1mA / ±(0.5%+5dgt)
Phase Voltage Peak1.0-1414V / 0.1 / ±(1.0%+5dgt)
Neutral Line voltage Peak1.0-2828V / 0.1 / ±(1.0%+5dgt)
Current Peak10mA-12727A / 1mA / ±(1.0%+5dgt)
CF1.0~3.99 / 0.01 / ±(1%+2dgt)4~9.99 / 0.01 / ±(5%+2dgt)
Active Power0.000W-9000.0kW / 0.001W / ±(1%+3dgt) PF>0.80.000W-9000.0kW / 0.001W / ±(1.5%+10dgt) 0.2<PF<0.8
Reactive Power, inductive orcapacitive0.000Var-9000.0kVar / 0.001Var / ±(1%+3dgt) PF<-0.50.000Var-9000.0kVar / 0.001Var / ±(1.5%+10dgt) -0.5<PF<-0.2
Apparent Power0.000VA-9000.0kVA / 0.001VA / ±(1%+3dgt)
Power Factor-1.000~1.000 / 0.001 / ±(1.5%+3dgt) PF>0.5-1.000~1.000 / 0.001 / ±(1.5%+10dgt) 0.2<PF<0.5
Active Electrical Energy0.000Wh-9000.0MWh / 0.001Wh / ±(1%+3dgt) PF>0.80.000Wh-9000.0MWh / 0.001Wh / ±(1.5%+10dgt) 0.2<PF<0.8
Reactive Electrical Energy, Inductive or Capacitive0.000Varh-9000.0MVarh / 0.001Varh / ±(1%+3dgt) PF<-0.50.000Varh-9000.0MVarh / 0.001Varh / ±(1.5%+10dgt) -0.5<PF<-0.2
Apparent Electrical Energy0.000VAh-9000.0MVAh / 0.001VAh / ±(1%+3dgt)
Phase Angle-179°~180° / 1° / ±2°
Tanφ (VA≥50VA)-32.76~32.76 / 0.001 / φ:±1°
DPF-1.000~1.000 / 0.001 / φ:±1°
Harmonic Ratio 1~50(Vrms>50V)0.0%~99.9% / 0.1% / ±(1%+5dgt)
Harmonic Angle(Vrms>50V)-179°~180° / 1° / ±3° 1-25th-179°~180° / 1° / ±10° 26-50th
Total HarmonicRatio (THD or THDF)≤500.0%~99.9% / 0.1% / ±(1%+5dgt)
Distortion Factor(DF or THD-R)≤500.0%~99.9% / 0.1% / ±(1%+10dgt)
Transformer K Factor1.00~99.99 / 0.01 / ±5%
3 Phase Unbalance0.0%~100% / 0.1% / ±1%
CT Turn Ratio
Expert mode
Harmonic1-50th
Total Harmonic distortion√ Per phase
Number of Transient Record150 groups
Voltage Flicker
Motor Starting Current detect100S
Three Phase Unbalance
Record960 days 1 second interval, 20 parameters each time
Min/Max
Alarm12800 groups of alarm records, 40 kinds of parameters are optional
Peak Value
Screenshot Capacity60
Comm portUSB
Withstand Voltage1min 3700Vac/50Hz,Case to line
Insulation10MΩ
Safety RegulationIEC-61010,CATIII 1000V/IEC61010-31/IEC61326
Display Mode640*480, 5.6inch, 116x88mm
Device Mode265x215x85mm
Instrument Weight1.6kgs(with battery),power adapter0.9kgs,Packing size with protective box and transformer, <15KGS
Power9.6V lithium battery
Power ConsumptionFully charged for 8 hours
MemoryBuilt-in 2G memory card
Waveform real-time display4 voltages/4 currents

Clients Reviews

Leave A Reviews